Charging & Circuit Service
In this course
4 sections, plus a graded quiz. Click any to jump to it.
Introduction
This is where refrigeration becomes a trade: weigh-in charging, evacuation, metering devices, and leak detection. These are the hands-on skills that make or break a refrigeration tech. The discipline here is non-negotiable — a system charged to guess fails in six months; a system charged to spec lasts.
Why it matters: an inadequate evacuation leaves moisture in the system, which reacts with the refrigerant and oil to form acids that destroy the compressor.
Weigh-in charging and evacuation
Weigh-in charging is the only reliable way to set a charge:
- Connect a scale to the liquid line.
- Weigh the system before and after adding refrigerant.
- Add exactly the amount the manufacturer specifies.
- Verify the superheat and subcooling are within spec.
Evacuation is the step before charging — you pull a vacuum to remove air and moisture before introducing refrigerant. The rule: evacuate to 500 microns or better, hold for 30 minutes, and verify the hold before charging.
TXV vs capillary: how they meter
A TXV (thermodynamic expansion valve) meters refrigerant flow based on the superheat at the evaporator outlet. It opens and closes automatically as the load changes. A capillary tube is a fixed-length, fixed-diameter tube that meters flow by restriction — it cannot adapt to changing load.
- TXV — the correct choice for variable-load applications (a walk-in that is sometimes full and sometimes empty).
- Capillary — acceptable for constant-load applications (a single cabin AC).
Remember this line: the metering device sets the flow into the evaporator. A failed TXV or
a blocked capillary starves the evaporator and reads as a compressor problem.
Leak detection: where to look first
A refrigerant leak in a marine system is almost always at a joint, not in a component. Check first:
- Compressor suction and discharge ports.
- Condenser connections.
- The expansion device.
- Evaporator connections.
Use an electronic leak detector at each joint. If you find a leak, repair it before you recharge. A system that has leaked and been recharged without repairing the leak is a system that will leak again.